- OBJECTIVE
To lay down the procedure for regeneration of mixed bed.
- SCOPE
This SOP is applicable in Water System for regeneration of mixed bed.
- RESPONSIBILITY
Water system operators/ Engineers | : | To follow the procedure |
- ACCOUNTABILITY
Head Engineering : System Compliance
- PROCEDURE
- Regenerate the mixed bed, after generation of approx 90 KL water or when the conductance increases from 1.0 µS/cm or pH does not comply the specification i.e 5.0 – 7.0, as per given below procedure.
- Back Wash:
- Flow Rate: 1.1 m3/hr.
- Washing Period : 15 minutes
- In feed water: RO Water.
- Close the valves V1 and V2.
- Open the valves V3, V4 &V12 and switch ON the MB feed pump.
- Left the system for 10 minutes.
- During back washing the flow of water should be in upward position.
- Off the water system and close all the valves.
- Caustic Injection
- Requirement : Sodium Hydroxide
Conditions
Flow Rate: 1.0 m3/hr.
- Time: 15 minutes.
- Infeed Water: RO Water
- Preparation of Sodium Hydroxide Solution: Prepare sodium hydroxide solution by dissolving 10 kg. Sodium Hydroxide pellets in 34 liters of RO water in a plastic carboy carefully.
- Open the valves V6, V7 and V2 and switch ON the MB feed pump. When the water flows then open the injector valve V5. This process takes 15 minutes.
- Caustic Rinse – Conditions:
Flow Rate: 0.175 m3/hr.
- Time:
30 minutes.
- In feed Water: R O Water.
- After completion of caustic injection close valve V5 and let the valves V7, V6 &V2 open. This process takes 30 minutes. During this process water flows from top to middle.
- After completion of process close all the valves.
- Acid Injection Second Cleaning:
- Requirement: 33 % Hydrochloric Acid.
- Conditions:
- Flow Rate: 0.167 m3/hr.
- Time: 15 minutes.
- In feed water: RO Water
- Preparation of 33 % Hydrochloric Acid: Take 21 liter Conc. Hydrochloric acid and mix in 60 liters RO water carefully in plastic carboy.
- Open the valves V9 and V10 and switch ON the MB feed pump. When the water flows then open the injector valve V8 & V1. This process takes 15 minutes.
- Acid Rinse:
- Conditions:
- Flow Rate: 0.25 m3/hr.
- Time : 36 minutes
- In feed Water : R O Water
- After completion of acid injection close valve V8 and let the valves V9, V10 & V1 open. This process takes 36 minutes. During this process water flows from middle to downwards.
- Conditions:
- Drain Down:
- Open the valves V10 and V12. This process takes 5 minutes.
- Air
Mixing:
- Air pressure: 0.5 kg / cm2
- Open the valves V11 and air outlet valve V12 and let the resin mixed. This process takes 10 minutes. During this process the air pressure should be maintained.
- After completion of process close the valve V11.
- Note: Air should be dried and oil free.
- Final
Rinse:
- Open the MB inlet valve V01 and rinse valve V10 and let the water flowed through column.
- Continue this process till the conductance reaches below 1.0 µS/cm & pH 5.0 to 7.0.
- Release
of Purified Water:
- When the conductance reaches below 1.0 µS/cm and pH between 5.0 & 7.0 then supervisor of water system inform to Quality Control Department to collect the water sample for testing.
- Q.C. Chemist should sample the water from the mixed bed sampling point and test the sample.
- After completion of analysis, Q.C. chemist should prepare the report and send to the water system.
- After release of water collect the purified water in the purified water storage tank.
- Write the detail in log sheet.
TRAINING
Trainer : Head – Quality Assurance& Engineering Department.
Trainees : Engineering- Executive & Supervisors.
DISTRIBUTION
Master Copy : Quality Assurance Department
Controlled Copy : Engineering Department
Display Copy : Engineering Department (If Required)
ATTACHMENTS
Sr. No. | Annexure No. | Title | Format No. |
1 | NA | NA | NA |
- REFERENCES
In-house
ABBREVIATION
Abbreviation | Extended Form |
EG | Engineering |
SOP | Standard Operating Procedure |
QA | Quality Assurance |
WH | Warehouse |
NA | Not Applicable |
MB | Microbiology |
11.0 REVISION HISTORY OF CHANGE
Sr. No. | Date | Revision Details | Revision No. |