CLEANING & SANITIZATION OF OVER HEAD POTABLE WATER STORAGE TANK

  1. OBJECTIVE

        To lay down the procedure for Cleaning & Sanitization of over head potable water storage tank.

  • SCOPE

This SOP is applicable in water system Cleaning & Sanitization of over head potable water storage tank.

  • RESPONSIBILITY
Water system operators/ Engineers  : To follow the procedure
  • ACCOUNTABILITY

Head Engineering                                :       System Compliance

  •    PROCEDURE:
    •            Cleaning:
      • Open the lid of the storage tank.
      • Drain the water from potable water storage tank.
      • Ensure proper lighting and air circulation inside the storage tank.
      • Prepared the 10 liter of sodium hypochlorite solution 1.0% in water (Take 100 ml of sodium hypochlorite add 9.9 lit of potable water in bucket) maintain the record of sodium hypochlorite solution preparation record.
      • Clean the storage tank walls with scrubber and rinse with water.
      • Drain the water.
      • Spray sodium hypochlorite solution 1.0% into the storage tank by using the spray container.
      • Close the lid of the tank and keep it for one hour.
      • Drain the water.
      • Use the tank for storage of Water and check chlorine in the water by using chlorine test kit. It should not be more than 2 ppm.
  • Take the storage tank for use.
    •       Maintain the record of sanitization and cleaning record of potable water storage tank.
    •            Frequency: At least once in three month (If required)

             TRAINING

Trainer   : Head – Quality Assurance& Engineering Department.

            Trainees: Engineering- Executive & Supervisors. 

  • DISTRIBUTION

Master Copy                     :           Quality Assurance

Controlled Copy               :           Engineering Department

Display Copy                    :           Engineering Department (if Required)

  ATTACHMENTS

  Sr. No. Annexure No. Title Format No.
1 NA NA NA
  • REFERENCES       

In-house

     ABBREVIATION

Abbreviation Extended Form
            EG Engineering
SOP Standard Operating Procedure
            QA Quality Assurance
WH Warehouse
NA Not Applicable

      REVISION HISTORY OF CHANGE